Daikin AC Error Codes Outdoor Units

0

 

Daikin AC Error Codes Outdoor Units

 

Fault Code Definition Supposed Causes Split Skyair VRV Package

E0

Protection devices tripped

Outdoor safety device tripped

E1

Failure of outdoor PCB

Defect of PCB or noise

E3

High pressure

High pressure switch tripped

E4

Low pressure

Low pressure switch tripped

E5

Inverter compressor lock

Inverter compressor locked

E5

Inverter compressor to hot

Compressor windings too hot

E6

DOL compressor locked

High current draw

E7

Fan motor failure

Failed fan motor, PCB

E8

Inv compressor high current

Compressor, PCB

E9

EEV motor failure

EEV motor, PCB

EA

4-way valve failure

Defect of valve, PCB, sensor

EC

Inlet water temperature

Abnormal water temperature

EF

Thermal storage unit defect

Thermal storage EEV, PCB, sensor

F3

High discharge temperature

Discharge temperature over 110°C

F6

High pressure in cooling

Detected by outdoor coil sensor

F6

Over charged

Refrigerant over charge

H0

Compressor sensor system

All sensors disconnected

H1

Failure of humidifier damper

Defect of limit switch/damper

H3

Failure of hp switch

High pressure switch open circuit

H4

Failure of lp switch

Low pressure switch open circuit

H5

Failure of compressor sensor

Defect of compressor overload sensor

H6

Compressor position failure

Position detection error

H7

Failure of fan motor signal

Defect of fan motor, PCB

H8

Compressor input error

Defect of transistor, PCB, reactor

H9

Failed ambient sensor

Sensor open short circuit

J1

Failed pressure sensor

Pressure sensor failed

J2

Failed current sensor

Defect of current sensor, PCB, compressor

J3

Failed discharge pipe sensor

Discharge pipe sensor open/short circuit

J4

Failed outdoor coil vapour sensor

Sensor open/short circuit

J5

Failed suction pipe sensor

Sensor open/short circuit

J6

Failed outdoor coil sensor

Sensor open/short circuit

J7

Failed liquid pipe sensor

Sensor open/short circuit

J8

Failed liquid pipe sensor

Sensor open/short circuit

J9

Failed sub cool heat exchanger sensor

Sensor open/short circuit

JA

Failed high pressure sensor

High pressure sensor open/short circuit

JC

Failed low pressure sensor

Low pressure sensor open/short circuit

JH

Failed oil temperature sensor

Open/short circuit

Trouble Shooting

Post a Comment

0Comments
Post a Comment (0)