Daikin AC System Error Codes

0

  

 

Daikin Error Codes

System Fault Codes

Fault Code Definition Supposed Causes Split Skyair VRV Package HRV

U0

Shortage of refrigerant

Undercharged, EEV fault, faulty sensor

U1

Reverse or missing phase

Reversed or missing phase

U2

Power supply fault

Power supply fault, capacitor wiring error

U3

Check operation not executed

Check operation not carried out at commissioning or after main PCB replaced

U4

Communication failure, between indoor & outdoor

Wiring fault, defect of PCB, pump wired across communication wiring

U5

Communication failure, between r/controller & PCB

Wiring fault, defect of Remote controller & PCB

U6

Communication failure between indoor units

Wiring fault, defect of indoor PCB

U7

Communication failure, between outdoor PCB’s

Defect of outdoor PCB, wiring error between PCB’s

U7 Communication failure Wiring error between outdoor units, • •

between outdoor units defect of outdoor PCB

U8 Communication failure be- Main/sub switch not set, wiring error, • • • •

tween remote controllers defect of remote controller

U9

System communication failed

Fault with other indoor unit, no power, A9

UA

Improper combination

Incorrect field setting, wiring, defect of PCB

UA

Incorrect field setting Wiring, defective PCB

Field setting incorrect (twin/triple), error in

UA

Improper combination of Indoor/outdoor units

Excess of indoor units, incorrect PCB Setting, defective PCB

UC Error in address setting Duplicated central control address • • • •

UE Communication failure Wiring error between indoor unit & central • • • •

between indoor central device control, defect of indoor PCB, setting error

UF Wiring/piping mismatch Wiring error indoor to outdoor, PCB defect • • •

UH

System malfunction

Unaddressed indoor unit

UH

System malfunction

Mismatched indoor/outdoor, freeze protect

UJ

Communication failure

Defect of accessory device, wiring error

M1

Central controller failed

Failure of central controller PCB

M8

Communication failure between central & options

Communication failed between central controller & optional controllers

MA

Improper combination of optional controllers

Incorrect settings, faulty central controller

MC

Duplicated address

Duplicated central controller address

60

Overall alarm

Open circuit across J1-JC

64

Failed return air sensor

Sensor open/short circuit

65

Failed ambient sensor

Sensor open/short circuit

6A

Failure of damper system

Defect of damper motor, limit switch, PCB